This paper presents the experimental tests on hybrid desiccant dehumidification and air conditioning systems. Experimental tests are carried out with desiccant at typical operative ranges for air conditioning applications, particularly for high humid regions like Hong Kong. Results are reported in terms of coefficient of performance (COP) based on primary energy usage and electrical energy usage, respectively. Experiments have demonstrated consistent reduction in humidity ratio satisfying the sensible as well as latent load through a respective subsystem and thereby resulting in a higher COP based on primary energy usage. Also, results show that the regeneration temperature as well as process air flow rate have a significant role on the system performance. It is found that the hybrid system can achieve a higher part load performance, and hence can assure of its effective operation all year around in hot humid regions.
Skip Nav Destination
Article navigation
February 2006
Research Papers
Experimental Study on a Hybrid Desiccant Dehumidification and Air Conditioning System
Li Yong,
Li Yong
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
Search for other works by this author on:
K. Sumathy,
K. Sumathy
Department of Mechanical Engineering,
University of Hong Kong
, Hong Kong
Search for other works by this author on:
Y. J. Dai,
Y. J. Dai
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
Search for other works by this author on:
J. H. Zhong,
J. H. Zhong
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
Search for other works by this author on:
R. Z. Wang
R. Z. Wang
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
Search for other works by this author on:
Li Yong
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
K. Sumathy
Department of Mechanical Engineering,
University of Hong Kong
, Hong Kong
Y. J. Dai
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
J. H. Zhong
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of China
R. Z. Wang
Institute of Refrigeration and Cryogenics,
Shanghai Jiao Tong University
, Shanghai, 200030, People's Republic of ChinaJ. Sol. Energy Eng. Feb 2006, 128(1): 77-82 (6 pages)
Published Online: March 28, 2005
Article history
Received:
December 24, 2004
Revised:
March 28, 2005
Citation
Yong, L., Sumathy, K., Dai, Y. J., Zhong, J. H., and Wang, R. Z. (March 28, 2005). "Experimental Study on a Hybrid Desiccant Dehumidification and Air Conditioning System." ASME. J. Sol. Energy Eng. February 2006; 128(1): 77–82. https://doi.org/10.1115/1.2148977
Download citation file:
Get Email Alerts
Mass Flow Control Strategy for Maximum Energy Extraction in Thermal Energy Storage Tanks
J. Sol. Energy Eng (December 2025)
Related Articles
A Liquid Desiccant System for Solar Cooling and Dehumidification
J. Sol. Energy Eng (August,2004)
Energy Saving Potential of a Combined Solar and Natural Gas-Assisted Vapor Absorption Building Cooling System
J. Sol. Energy Eng (February,2019)
A Study of the Performance of a Hybrid Liquid Desiccant Cooling System Using Lithium Chloride
J. Sol. Energy Eng (February,2003)
Dehumidification and Simultaneous Removal of Selected Pollutants from Indoor Air by a Desiccant Wheel Using a 1M Type Desiccant
J. Sol. Energy Eng (February,1999)
Related Proceedings Papers
Related Chapters
Two-Stage Liquid Desiccant Dehumidification∕Regeneration
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)
A Method Based on the Fluctuation of the Temperature Difference to Select the Zeotropic Refrigerant Mixture in the Air-Conditioning Condition
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)
Numerical Simulation and Analysis about Harmonic Performance Used for Heat Transfer and Air-Conditioning Cooling Load of Energy-Saving Porous Brick and Hollow Brick Wall
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)